×

INGENIO PLUS

3-phase UPS 30-160 kVA

Low TCO, efficient and compact solution for supplying reliable uninterrupted quality power to all critical applications in networking and small to medium data center, health, finance, industrial processing, building and transportation markets and for TLC.

Featuring Green Conversion patented technology, INGENIO PLUS provides high efficiency even at light loads and ensures 100% battery expected life, thus ensuring low opex and capex savings.

  • Continuous savings with Green Conversion patented technology, providing high efficiency and UPS critical components’ life care.
  • No costs related to electrical infrastructure oversizing and power factor correction thanks to its 0.99 input PF.
  • Reduced commissioning and floor space related costs and lower environmental footprint with transformer free design and common battery management option.
  • High flexibility for all types of loads with full output power rating and different high efficiency operating modes.
  • Green Conversion technology, high efficiency even at light load and the lowest TCO in its category.
  • Full rated output power, ensuring optimal UPS sizing and utilization.
  • Transformer free design for compact, light and sustainable systems.
  • Full IGBT technology and electronic PFC, ensuring 0.99 input PF and THDi <3% for maximum upstream sources compatibility.
  • Dynamic Charging Mode (DCM) for maximum versatility in long autonomy and low charging time applications.
  • Common battery (on 60-160 kVA range) management option for even more compact and cost saving UPS systems.
  • Comprehensive set of communication options for total remote monitoring of equipment operation.

Tech Specs

INGENIO PLUS: 3-phase UPS 30-160 kVA

Rating (kVA) 30 40 60 80 100 125 160
Nominal power (kW) 30 40 60 80 100 125 160
UPS dimensions WxDxH (mm) 460x650x1230 560x940x1500 560x940x1800
UPS weight (kg) 120 140 190 215 320 360 380
UPS weight
with int. battery (kg)
365 385 770 785 - - -
Battery configuration Internal or external, 360 to 372 cells, VRLA (other options) External 360 to 372 cells, VRLA (other options)
Max autonomy with int.
battery 70% load (min)
11 7 12 8 - - -

Input

Connection type Hardwired 4w Hardwired 4w (rectifier), 4w (bypass)
Nominal voltage 400 Vac 3-phase with neutral (rectifier)
380/400/415 Vac 3-phase with neutral (bypass)
Voltage tolerance -20%, +15% (rectifier); ±10% (bypass)
Frequency and range 50/60 Hz, 45 to 65 Hz
Power factor >0.99
Current distortion (THDi) <3%

Output

Connection type Hardwired 4w
Nominal voltage 380/400/415 Vac 3-phase with neutral
Frequency 50/60 Hz
Voltage regulation Static: ±1%;
dynamic: IEC/EN 62040-3 Class 1
Power factor Up to 1, without power derating
Overload capacity* Inverter: 110% for 10 min, 125% for 5 min, 150% for 30;
bypass: 150% continuous, 1000% for 1 cycle
Efficiency (AC/AC)** Up to 99%
Classification as per IEC EN 62040-3 VFI-SS-11

*conditions apply **according to IEC/EN 62040-3

Connectivity and function extensions

Front panel Graphic display, mimic LED panel and keyboard, local EPO
Remote communication Included (30 to 160 kVA): backfeed protection monitoring contact.
Included (60 to 160 kVA): serial RS232 and USB; input terminal block (remote emergency power off, battery circuit breaker aux. cont. external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.).
Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet), ModBus-RTU (RS485), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software
Optional function extensions Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets;
wall-mounted battery fuse switch box; battery thermal probe; parallel kit, load-sync for single UPS and load-sync box (2 UPS systems);
other options on request

System

Protection degree IP 20
Colour RAL 9005
Installation layout 10 cm wall-gap, side by side installation allowed Wall and side by side installation allowed, 80 cm clearance on one side with internal battery
Accessibility Front and top access, bottom cable entry Front and top access, side access (with internal battery) bottom cable entry Front access, side access (with internal battery), bottom cable entry

Environmental

UPS operating temperature 0°C to +40°C
UPS storage temperature -10°C to +70°C
Altitude (AMSL) < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m
Audible noise at 1 m (dBA) <60

Standards and certifications

Quality assurance, environment,
health and safety
ISO 9001, ISO 14001, ISO 45001
Safety IEC/EN 62040-1
EMC IEC/EN 62040-2
Environmental aspects IEC/EN 62040-4
Test and performance IEC/EN 62040-3
Protection degree IEC 60529
Marking CE
Your membership cannot be validated.
Your registration was successful.

Newsletter

Subscribe to our newsletter and stay updated

Utilizziamo Brevo come nostra piattaforma di marketing. Cliccando qui sotto per inviare questo modulo, sei consapevole e accetti che le informazioni che hai fornito verranno trasferite a Brevo per il trattamento conformemente alle loro condizioni d'uso

TOP