Ingenio Compact three-phase UPS provides a perfect solution for critical power applications such as networks and servers, small and medium data centers, telecommunication. Ingenio Compact is a three-phase UPS available in the 10-20 kVA range with on-line double conversion technology and parallel redundant configuration.
Rating (kVA) | 10 | 15 | 20 |
Nominal power (kW) | 10 | 15 | 20 |
UPS dimensions WxDxH (mm) | 440x800x800 | ||
UPS weight (kg) | 75 | 76 | 76 |
UPS weight with internal battery (kg) | 150 | 165 | 165 |
External battery module dimensions WxDxH (mm) |
550x650x1200 | ||
Battery configuration | Internal (standard): 180 cells; external: 156/240 cells | Internal (standard): 216 cells; external: 192/240 cells |
Connection type | Hardwired 4w | ||
Nominal voltage | 400 Vac 3-phase with neutral | ||
Voltage tolerance | -20%, +15% (rectifier); ±10% (bypass) | ||
Frequency and range | 50/60 Hz, 45 to 70 Hz | ||
Power factor | 0.99 | ||
Current distortion (THDi) | <3% |
Connection type | Hardwired 4w | ||
Nominal voltage | 380/400/415 Vac 3-phase with neutral | ||
Frequency | 50/60 Hz | ||
Power factor | Up to 1, without power derating | ||
Overload capacity | 110% for 60 min, 125% for 10 min, 150% for 1 min | ||
Efficiency (AC/AC)* | Up to 98% | ||
Classification by IEC/EN 62040-3 | VFI-SS-11 |
*according to IEC/EN 62040-3
Front panel | Touch screen display | ||
Remote communication | Included: serial RS232; backfeed protection monitoring contact, remote EPO contact. Optional: 2 slots for SNMP adapter, ModBus-RTU, contact relay card |
||
Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit; other options on request |
Protection degree | IP 20 | |
Colour | RAL 9005 | |
Installation layout | 30 cm wall-gap | |
Accessibility | Positioning casters; bottom cable entry |
UPS operating temperature range | 0°C to +40°C | |
UPS storage temperature range | -10°C to +70°C | |
Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m | |
Audible noise at 1 m (dBA) | <52 |
Quality assurance, environment, health and safety |
ISO 9001:2015, ISO 14001:2015, BS OHSAS 18001:2007 | |
Safety | IEC/EN 62040-1 | |
EMC | IEC/EN 62040-2 | |
Environmental aspects | IEC/EN 62040-4 | |
Test and performance | IEC/EN 62040-3 | |
Protection degree | IEC 60529 | |
Marking | CE |