Low TCO, efficient and compact solution for supplying reliable uninterrupted quality power to all critical applications in networking and small to medium data center, health, finance, industrial processing, building and transportation markets and for TLC.
Featuring Green Conversion patented technology, INGENIO PLUS provides high efficiency even at light loads and ensures 100% battery expected life, thus ensuring low opex and capex savings.
Rating (kVA) | 30 | 40 | 60 | 80 | 100 | 125 | 160 |
Nominal power (kW) | 30 | 40 | 60 | 80 | 100 | 125 | 160 |
UPS dimensions WxDxH (mm) | 460x650x1230 | 560x940x1505 | 560x940x1800 | ||||
UPS weight (kg) | 120 | 140 | 210 | 225 | 320 | 360 | 380 |
UPS weight with int. battery (kg) |
365 | 385 | 770 | 785 | - | - | - |
Battery configuration | Internal or external, 360 to 372 cells, VRLA (other options) | External 360 to 372 cells, VRLA (other options) | |||||
Max autonomy with int. battery 70% load (min) |
11 | 7 | 12 | 8 | - | - | - |
Connection type | Hardwired 4w | Hardwired 4w (rectifier), 4w (bypass) |
Nominal voltage | 400 Vac 3-phase with neutral (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
|
Voltage tolerance | -20%, +15% (rectifier); ±10% (bypass) | |
Frequency and range | 50/60 Hz, 45 to 65 Hz | |
Power factor | >0.99 | |
Current distortion (THDi) | <3% |
Connection type | Hardwired 4w |
Nominal voltage | 380/400/415 Vac 3-phase with neutral |
Frequency | 50/60 Hz |
Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
Power factor | Up to 1, without power derating |
Overload capacity* | Inverter: 110% for 10 min, 125% for 5 min, 150% for 30 s, >150% for 0.1 s; bypass: 150% continuous, 1000% for 1 cycle |
Efficiency (AC/AC)** | Up to 99% |
Classification as per IEC EN 62040-3 | VFI-SS-111 |
*conditions apply **according to IEC/EN 62040-3
Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
Remote communication | Included (30 to 160 kVA): backfeed protection monitoring contact. Included (60 to 160 kVA): serial RS232 and USB; input terminal block (remote emergency power off, battery circuit breaker aux. cont. external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.). Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet), ModBus-RTU (RS485), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment;
external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
Protection degree | IP 20 | ||||||
Colour | RAL 9005 | ||||||
Installation layout | 10 cm wall-gap, side by side installation allowed | Wall and side by side installation allowed, 80 cm clearance on one side with internal battery | |||||
Accessibility | Front and top access, bottom cable entry | Front and top access, side access (with internal battery) bottom cable entry | Front access, side access (with internal battery), bottom cable entry |
UPS operating temperature | 0°C to +40°C |
UPS storage temperature | -10°C to +70°C |
Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
Audible noise at 1 m (dBA) | <60 |
Quality assurance, environment, health and safety |
ISO 9001:2015, ISO 14001:2015, BS OHSAS 18001:2007 |
Safety | IEC/EN 62040-1 |
EMC | IEC/EN 62040-2 |
Environmental aspects | IEC/EN 62040-4 |
Test and performance | IEC/EN 62040-3 |
Protection degree | IEC 60529 |
Marking | CE |