Borri E8000 ECS Emergency Central Systems have been designed in compliance to the international EN 50171 standard, supplying uninterrupted quality power to emergency and safety installations, such as:
Rating (kVA) | 10 | 15 | 20 | |||
Nominal power (kW) | 9 | 13.5 | 18 | |||
Nominal power as per EN 50171 (kW) | 7.5 | 11.3 | 15 | |||
UPS dimensions WxDxH (mm) |
450x670x1200 | |||||
UPS weight (kg) | 100 | 110 | 110 | |||
Battery | External, 360 to 372 cells, VRLA (other options) |
Connection type | 3/1-phase units: hardwired 4w (rectifier), 2w (bypass) 3/3-phase units: hardwired 4w (separate bypass input available on request) |
||
Nominal voltage | 400 Vac 3-phase with neutral (rectifier) 220/230/240 Vac (3/1-phase bypass) |
||
Voltage tolerance | -20%, +15% (rectifier) ±10% (bypass) | ||
Frequency and range | 50/60 Hz, 45 to 65 Hz | ||
Power factor | 0.98 | ||
Current distortion (THDi) | <4% |
Connection type | 3/1-phase units: hardwired 2w 3/3-phase units: hardwired 4w |
||
Nominal voltage | 3/1-phase units: 220/230/240 Vac 1-phase 3/3-phase units: 380/400/415 Vac 3-phase with neutral |
||
Frequency | 50/60 Hz | ||
Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 | ||
Power factor | Up to 0.9, without power derating | ||
Overload capacity* | 120% continuous; 150% for 10 min; | ||
Efficiency (AC/AC)** | Up to 98% | ||
Classification as per IEC/EN 62040-3 | VFI-SS-11 |
*as per EN 50171 **as per IEC/EN 62040-3
Front panel | Graphic display, mimic LED panel and keyboard, local EPO | ||
Remote communication | Included: serial RS232 and USB; terminal block for battery breaker auxiliary contact.
Optional: input terminal block (remote emergency power off, external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.); SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet), ModBus-RTU (RS485), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
||
Optional features | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; load-sync for single UPS; AO+EO mode kit; separate input for rectifier and bypass line (for 3-phase output models); parallel kit; other options on request |
Protection degree | IP 20 | ||
Colour | RAL 7016 | ||
Installation layout | 10 cm wall-gap, side by side installation allowed | ||
Accessibility | Front and top access, bottom cable entry |
Operating temperature range | 0°C to +40°C | ||
Storage temperature range | -10°C to +70°C | ||
Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m | ||
Audible noise at 1 m (dBA) | <52 |
CPSS | EN 50171 | ||
Quality assurance, environment, health and safety |
ISO 9001:2015, ISO 14001:2015, BS OHSAS 18001:2007 | ||
Safety | IEC/EN 62040-1 | ||
EMC | IEC/EN 62040-2 | ||
Environmental aspects | IEC/EN 62040-4 | ||
Test and performance | IEC/EN 62040-3 | ||
Protection degree | IEC 60529 | ||
Marking | CE |