Three-phase output Uninterruptible Power Supplies for heating, ventilation and air conditioning equipment, safety and emergency systems, process control devices and machine tooling, critical infrastructures, medical equipment, data center monolithic power protection.
Rating (kVA) | 400 | 500 | 600 | 800 |
Nominal power (kW) | 360 | 450 | 540 | 720 |
Dimensions WxDxH (mm) | 1990x950x1920 | 2440x950x2020 | 2440x950x2020 | 3640x950x1920 |
UPS weight (kg) | 1955 | 2482 | 2535 | 3600 |
Battery configuration | External, 300 to 312 cells, VRLA (other options) |
Connection type | Hardwired 3w (rectifier), 4w (bypass) | |||
Nominal voltage | 400 Vac 3-phase (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
|||
Voltage tolerance | -20%, +15% (rectifier); +10% (bypass) | |||
Frequency and range | 50/60 Hz, 45 to 65 Hz | |||
Power factor | 0.99 | |||
Current distortion (THDi) | <3% |
Connection type | Hardwired 4w | |||
Nominal voltage | 380/400/415 Vac 3-phase with neutral | |||
Frequency | 50/60 Hz | |||
Voltage regulation | Static ±1%; dynamic: IEC EN 62040-3 Class 1 | |||
Power factor | Up to 0.9, without power derating | |||
Overload capacity | Inverter: 125% for 10 min, 150% for 1 min, 199% for 10 s; bypass: 150% continuous, 1000% for 1 cycle |
|||
Efficiency (AC/AC)* | Up to 98% | |||
Classification as per IEC EN 62040-3 |
VFI-SS-11 |
*according to IEC EN 62040-3
Front panel | Graphical display, mimic with LED and keyboard, local EPO | |||
Remote communication | Included: serial RS232 and USB; input terminal block for: remote emergency power off (REPO), battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.. Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet); ModBus-RTU (RS485); ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
|||
Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment;
maintenance bypass switch in extended cabinet or wall-mounted box; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit; top cable entry; load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
Protection degree | IP 20 (other options) | |||
Colour | RAL 7016 (other options) | |||
Installation layout | Wall, back to back and side by side installation allowed | |||
Accessibility | Front and top access, bottom cable entry |
Operating temperature range | 0°C to +40°C | |||
Storage temperature range | -10°C to +70°C | |||
Altitude (AMSL) | <1000 m without power protection, >1000 m with reduction of 0.5% per 100 m | |||
Audible noise at 1 m (dBA) | <62 |
Quality assurance, environment, health and safety | ISO 9001:2015, ISO 14001:2015, BS OHSAS 18001:2007 | |||
Safety | IEC EN 62040-1 | |||
EMC | IEC EN 62040-2 | |||
Environmental aspects | IEC EN 62040-4 | |||
Test and performance | IEC EN 62040-3 | |||
Protection degree | IEC 60529 | |||
Marking | CE |