Industrial, heavy duty Inverter with galvanic insulation. Designed to Supply critical AC loads with stabilized continuous supply, in the Oil & Gas, Petrochemical, Power & Utilities applications.
Rating (kVA) | 5 | 10 | 15 | 20 | 30 | 40 | 50 | 5 | 10 | 15 | 20 | 30 | 4 | 50 | 60 | 80 | 100 |
Nominal power (kW) | 4 | 8 | 12 | 16 | 24 | 32 | 40 | 4 | 8 | 12 | 16 | 24 | 32 | 40 | 48 | 64 | 80 |
Rating (kVA) | 5 | 10 | 15 | 20 | 30 | 40 | 50 | 5 | 10 | 1 | 20 | 30 | 40 | 50 | 60 | 80 | 100 |
DC input voltage | 110 Vdc (90÷160 Vdc range) | 220 Vdc (180÷300 Vdc range) | |||||||||||||||
Bypass input voltage | 110/115/120 or 220/230/240 Vac 1-phase ±20% (adjustable according to inverter output voltage) |
Nominal voltage | 110/115/120/220/230/240 Vac 1-phase |
Frequency | 50/60 Hz (selectable) |
Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms |
Harmonic Distortion THDv |
<2% linear load; <5% non-linear load |
Isolation | Battery to load isolation included; input/output isolation available with additional bypass transformer | |||||||||||||||||
Dimensions WxD (mm) | Height is 2100 mm, width and depth vary with output rated power and voltage (see the table below) | |||||||||||||||||
Rating | 5 | 10 | 15 | 20 | 30 | 40 | 50 | 5 | 10 | 15 | 20 | 30 | 40 | 50 | 60 | 80 | 100* | |
Output voltage | 110÷120 Vac | 600x800 | 800x800 | 1000x800 | 600x800 | 800x800 | 1000x800 | 1400x800 | ||||||||||
220÷240 Vac | 600x800 | 800x800 | 1000x800 | 600x800 | 800x800 | 1400x800 | ||||||||||||
Maximum weight (kg) | 320 | 360 | 400 | 440 | 500 | 550 | 610 | 320 | 360 | 400 | 440 | 470 | 500 | 550 | 600 | 730 | 830 | |
Cooling | Forced ventilation | |||||||||||||||||
Efficiency | 94% | |||||||||||||||||
Colour | RAL 7035 | |||||||||||||||||
Protection degree (IEC 60529) | IP20 (other options) |
Operating temperature | -10 °C ÷ +40 °C |
Storage temperature | -20 °C ÷ +70 °C |
Altitude | <2000 m (derating according to EN 62040-3) |
Audible noise at 1 meter (dBA) | <65÷75 |
Options | Associated distribution panels; emergency line isolation transformer and AC/AC voltage stabilizer; parallel redundant, hot-standby, load-sync configuration; earth fault alarm; fan monitoring and alarm; redundant ventilation; additional RFI filters; top cable entry. |
Front panel | LCD display, LED mimic, keyboard. Customisable status and alarms LED set |
Connectivity | SPDT contact relay card, RS232 serial port Optional: RS485 ModBus-RTU serial port, ModBus to PROFIBUS DP adapter, Ethernet SNMP/WEB adapter, remote monitoring software, up to 2 additional SPDT contact relay cards. |
*400 Vac